Altistart 01 Soft Starters Page 29 Wiring Diagrams

29 Altistart 01 & U01 soft starters for asynchronous motors ATS01N2 pppp & ATSU01N2 pppp Wiring Diagrams Altistart 01 soft starter and TeSys U-Line motor starter combinations Automatic 3-wire control with soft stop 120 Vac Supply S1 STOP 18 17 Fuse LUB LUA1C20 L TeSys U-line L1 L2 L3 M 3~ BOOST 2/T1 ( 1 ) ( 3 ) ( 2 ) LO1 LI1 LI2 COM LI+ A1 R1A R1C 1/L1 6/T3 4/T2 M1 5/L3 3/L2 14 13 A1 A2 LUB 208-480 V S2 START N ATS01N2 pp LU/QN/RT START 18 17 S1 STOP 24 Vdc Supply LUA1C20 LUB + S2 TeSys U-line L1 L2 LUB L3 M LUB 3~ BOOST 2/T1 ( 1 ) ( 2 ) LO1 LI1 +24 V LI2 COM A1 R1A R1C 1/L1 4/T2 6/T3 M1 3/L2 5/L3 13 14 A1 LUB A2 - 208-480 V ATSU01N2 pp LT 10 s t1 t2 V 1 Line voltage Logic input LI1 Pushbutton S1 Logic input LI2 Pushbutton S2 Yellow LED Logic output LO1 Motor voltage Notes: A1: ATS01 soft starter LUB: TeSys U-Line motor starter LUA1C20: Control circuit contact block for TeSys U-Line motor starter S1, S2: Momentary pushbuttons t1: 1 - 10 second adjustable starting time t2: 1 - 10 second adjustable stopping time V1: Initial motor voltage - adjustable from 30 to 80% of the motor's rated voltage (1) Optional jumper to select boost (2) See page 11 for L01 wiring recommendations (3) Use shielded cable if control wiring is longer than 3 feet

Previous Page