Altistart 01 Soft Starters Page 37 Wiring Diagrams

37 Altistart 01 & U01 soft starters for asynchronous motors ATS01N2 pppp & ATSU01N2 pppp Wiring Diagrams FU3 3~ LI1 BOOST ( 4 ) ( 3 ) LO1 LI2 LI+ M1 2/T1 4/T2 6/T3 A1 COM R1A R1C 1/L1 5/L3 3/L2 ( 1 ) ( 2 ) Q1 Starter L1 208-480 V L3 L2 ATS01N2 pp LU/QN/RT soft starter with GV manual starter, or other motor starter Manual control without soft stop t1 10 s Line voltage/ Green LED Yellow LED Motor voltage LO1 t V 1 Notes: A1: ATS01 soft starter FU3: Fast-acting UL Listed Class J fuse Q1: Manual motor starter or disconnect switch t1: 1 - 10 second adjustable starting time t2: 1 - 10 second adjustable stopping time V1: Initial motor voltage - adjustable from 30 to 80% of the motor's rated voltage (1) Fuses are not required if device Q1 is a GV manual motor starter installed per local and national electrical codes. (2) Overload protection is required if not included on device Q1. (3) Optional jumper to select boost. (4) See page 11 for L01 wiring recommendations