Altistart 48 Enclosed Altistart 48 Soft Starters Page 32 Wiring Diagrams

32 Altistart 48 soft starters for asynchronous motors Non-reversing w/ shunt trip fault isolation Wiring Diagrams 120V TS TR * TRIP RELAY FAULT RELAY ST* CB SHUNT TRIP COIL * TS RCR * RUN COMMAND RELAY TS SCA* SHORTING CONTACTOR PILOT RELAY TS SC * SHORTING CONTACTOR FR TR (2 SEC) (A) (B) 3 2 MOTOR THERMAL SW 4 5 (R2A) (R2C) END START UP SCA G* RUN R* POWER ON SEE DETAIL A (C) RCR TS FR * * (R1A) (R1C) FAULT FU4 FU1 FU2 FU3 CL2 T1 1 M SC A B C SC 2 6/T3 C2 4/T2 B2 2/T1 5/L3 3/L2 1/L1 A2 AC LINE SUPPLY * = User supplied 1 2 3 4 5 For shorting contactor operation, add SC with associated control circuit. Relay contact located on ATS48 controller. Located at motor. Jumper if switch not present. Connect control power transformer for 120 V secondary voltage. Use RCR relay logic for 120 V control of the ATS48. For 24 Vdc control, omit the RCR relay logic and wire controls directly to the ATS48 (see DETAIL B). DETAIL A (120 V RCR CONTROL) OFF ON R O STOP START 2-WIRE CONTROL W / O AUTO 3-WIRE CONTROL (A) (B) HAND OFF AUTO 2-WIRE CONTROL W / AUTO REMOTE START (A) (C) (B) (A) (B) Circuit Breaker w/Shunt Trip * FU4 D N G 1 L C CL2 STOP RUN LI3 LI4 +24V LO+ LO1 LO2 AO1 COM PTC1 PTC2 R1A R1C FAULT R2A R2C R3A R3C END START UP PROGRAMMABLE N.O. CONTACT ATS48 SOFT START TO CONTROL POWER TRANSFORMER { SEE DETAIL B OFF ON +24V RUN STOP OR RCR +24V RUN STOP +24V RUN STOP 120 V RCR CONTROL 2-WIRE 24 VDC CONTROL 3-WIRE 24 VDC CONTROL Non-reversing with shunt trip fault isolation