Home / altivar-12-variable-speed-drives / Page 13

Altivar 12 Variable Speed Drives - Page 13 Selection Tables

13

Altivar 12 variable speed drives

Short Circuit Current Ratings

ATV12 Drive Short Circuit Current Ratings

(1)

Input Voltage +10%/ -15% 60 Hz Y HP kw Input with- stand Rating (kA)

(6)

Part number With QO Circuit Breaker With GV2P/3P With Fuses

QO QOB QOU A SCCR (kA)

(7)

x GV2P/3P Type E

(2)(3)

SCCR (kA) FUses (A)

(5)

Z1, Z2 SCCR (kA) Line Reac- tor

(4)

120 V, 1 phase 0.25 0.18 1 ATV12H018F1 yes yes yes 10 1 GV2P10 1 Ferraz HSJ (15) 1

-

0.5 0.37 1 ATV12 p 037F1 yes yes yes 20 1 GV2P14 1 Ferraz HSJ (25) 1

-

1 0.75 1 ATV12H075F1 yes yes yes 25 1 GV2P20 1 Ferraz HSJ (40) 1

-

240 V, 1 phase 0.25 0.18 1 ATV12H018M2 yes yes yes 10 1 GV2P08 1 Fast Acting Class CC Ferraz TDR (7) 1

-

0.5 0.37 1 ATV12 p 037M2 yes yes yes 10 1 GV2P10 1 Ferraz HSJ (15) 1

-

0.75 0.55 1 ATV12 p 055M2 yes yes yes 15 1 GV2P14 1 Ferraz HSJ (25) 1

-

1 0.75 1 ATV12 p 075M2 yes yes yes 20 1 GV2P14 1 Ferraz HSJ (25) 1

-

2 1.5 1 ATV12HU15M2 no no yes 25 1 GV2P20 1 Ferraz HSJ (40) 1

-

3 2.2 1 ATV12HU22M2 no no yes 35 1 GV2P22 1 Ferraz HSJ (45) 1

-

240 V, 3 phase 0.25 0.18 5 ATV12H018M3 yes yes yes 10 5 GV2P07 5 Fast Acting Class CC Ferraz ATDR (7) 5

-

0.5 0.37 5 ATV12 p 037M3 yes yes yes 10 5 GV2P08 5 Fast Acting Class CC Ferraz ATDR (7) 5

-

1 0.75 5 ATV12 p 075M3 yes yes yes 15 5 GV2P14 5 Ferraz HSJ (15) 5

-

2 1.5 5 ATV12 p U15M3 yes yes yes 15 5 GV2P16 5 Ferraz HSJ (25) 5

-

3 2.2 5 ATV12 p U22M3 yes yes yes 25 5 GV2P20 5 Ferraz HSJ (25) 5

-

- 3 5 ATV12 p U30M3 no no yes 30 5 GV2P21 5 Ferraz HSJ (40) 5

-

5 4 5 ATV12 p U40M3 no no yes 40 5 GV2P22 5 Ferraz HSJ (45) 5

-

240 V, 3 phase 0.25 0.18 5 ATV12H018M3 yes yes yes 10 10 GV2P07 50 3 65 3% 0.5 0.37 5 ATV12 p 037M3 yes yes yes 10 10 GV2P08 50 8 65 3% 1 0.75 5 ATV12 p 075M3 yes yes yes 15 10 GV2P14 50 15 65 3% 2 1.5 5 ATV12 p U15M3 yes yes yes 15 10 GV2P13 50 25 65 3% 3 2.2 5 ATV12 p U22M3 yes yes yes 25 10 GV2P18 50 30 65 3% - 3 5 ATV12 p U30M3 no no yes 30 10 GV2P25 50 40 65 3% 5 4 5 ATV12 p U40M3 no no yes 40 10 GV2P32 50 50 65 3%

(1) Types of enclosures that can be used: 1, 12, 3, 3R, 4, and 4X-all non-ventilated. (2) The GV2Ppp self-protected manual combination starter must be used with the GV2GH7 insulating barrier to meet the UL 508 Type E rating. (3) The GV3Ppp self-protected manual combination starter must be used with the GV3G66 insulating barrier and the GVAM11 auxiliary contact block to meet the UL 508 Type E rating. (4) The line reactor is required when the ATV12 drive is used in a system with a current availability higher than the drive's SCCR design (5) When fuse type is not specified any Class J or CC can be used. If fuse manufacturer is not specified any fuse manufacturer can be used. (6) Input withstand rating is that for which the product has been designed thermally. Installation on a supply greater than this level will require additional inductance to satisfy this level (7) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes. This is dependant on the type of installation. Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kiloAmperes,___Y___Volts maximum, when protected by___Z1___with a maximum rating of___Z2___.

Previous Page