Altivar 1260 Medium Voltage Drives Page 38 Outline drawings

Dimensions & Weights 38 Altivar 1260 MV variable speed drive Overload 115% for 60 seconds Dimensions to nearest inch Weight in Lbs Based on estimated pf = .89 and motor efficiency = .96 Drive (H x D) 109" (90" w/o fan) x 43" Transformer (H x D) 110" X 43" HVL/cc switch (H X D) 90" x 37" HVL/cc Switch (optional) x1, x2, x3 (based on HP) Close-coupled or separate transformer Switch (optional) Rectifier Transformer VFD Grid topology Rated Converter KVA Rated HP (motor shaft) Rated Output Current (A) Width WT Width WT Width WT 24P DFE 610 700 85 15 480 67 6,500 79 4,408 24P DFE 698 800 97 15 480 67 6,500 79 4,408 24P DFE 872 1000 121 15 480 67 7,000 79 4,408 24P DFE 1090 1250 151 15 480 72 8,200 79 4,408 24P DFE 1308 1500 182 15 480 72 8,200 79 4,408 24P DFE 1526 1750 212 15 480 72 8,200 79 4,408 24P DFE 1744 2000 242 15 480 72 9,500 79 4,408 24P DFE 2093 2400 290 15 480 87 11,200 79 4,408 24P DFE 2441 2800 339 15 480 87 11,200 158 8,375 24P DFE 2790 3200 387 15 480 87 11,700 158 8,375 24P DFE 3139 3600 436 15 480 112 13,200 158 8,375 24P DFE 3488 4000 484 15 480 112 13,200 158 8,375 24P DFE 4011 4600 557 15 480 112 15,000 158 8,375 24P DFE 4185 4800 581 15 480 120 16,400 158 8,375 36P DFE 4534 5200 629 15 480 120 16,400 236 11,464 36P DFE 5057 5800 702 15 480 120 18,100 236 11,464 36P DFE 5668 6500 787 15 480 132 19,400 236 11,464 4,160V air cooled with standard sine wave filter