Altivar 312

variable speed drives

Functions

Functions

(continued)

Motor thermal protection The theoretical temperature rise of the motor is continuously calculated to provide indirect thermal protection. Thermal protection is adjustable from 0.2 to 1.5 times the nominal drive current. This function is suitable for all applications with self-cooled motors. Drive thermal protection Thermal protection, by a PTC probe mounted on the heatsink or integrated in the power module, ensures that the drive is protected in the event of poor ventilation or excessive ambient temperatures. Locks the drive in the event of a detected fault. R1/R2 relay configuration The following states are signalled when the relay is powered on: Drive detected fault Drive running Frequency threshold reached High speed reached Current threshold reached Frequency reference reached Motor thermal threshold reached Brake sequence (R2 only)

10 000 ( 2 h 45) 1 000 100 0,7 0,8 0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 50 20 10 1 3 5 Hz ( 16 mn)

Motor current/ItH t Trip time in seconds

Motor thermal protection curves

5000 3000 1000 200 160 100 60 2 0 1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9

t Motor current/Drive In Trip time in seconds

Drive thermal protection curves