Altivar 61 And Altivar 61 Plus Variable Speed Drives Page 23 Selection Tables

23 Altivar 61 variable speed drives Short Circuit Current Ratings (1) This column shows the maximum prospective short circuit current value that cannot be exceeded without adding input impedance. Electrical distribution systems with a higher prospective short circuit current will cause higher input currents in the front end of the drive. It is possible for the tested SCCR rating of the drive to be lower than this Input rating. The tested SCCR rating can be higher than this input rating when a line reactor is used. (2) An ATV61 output short circuit test was performed for 100 kA. In addition to providing a rating based on shorting the output of the drive, these short circuit rating have been obtained by shorting components internal to the Altivar 61. These ratings allow proper coordination of short circuit protection. The integral solid state short circuit protection in the drive does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any local codes. The listed line reactor or minimum impedance is required to obtain ratings above the Input Rating. (3) Ratings apply to an Altivar 61 mounted in a non-ventilated Type 1, 3R, 4(X) or 12 rated enclosure. Use noted ratings when using a Type 1 conduit kit. Minimum enclosure volume allows for the specified SCCR. Your application specific thermal requirements may require a larger enclosure. (4) The fuse ratings in this column are for an Altivar 61 drive installed with a VW3A92pppp Type 1 conduit kit. These fuse ratings in this column can also apply to Altivar 61 drive installed in a Type 1, 3R, 4(X) or 12 rated enclosure that has a minimum volume listed in the table. (5) Circuit breakers with lower interrupt ratings can be used within the same circuit breaker frame rating. For 200 / 240 Vac, replace with HGL or JGL for 65kA interrupt rating. For 380 / 480 Vac, replace with HGL or JGL for 35kA or HJL or JJL for 65kA interrupt rating. For 500 / 600 Vac, replace with HJL for 25kA or HGL for 18kA, or HDL for 14kA interrupt rating. (6) 480 V ratings are for Wye connected electrical distribution systems only. GV2Ppp self protected manual combination starter must be used with GV2GH7 insulating barrier to meet UL 508 Type E rating GV3Ppp self protected manual combination starter must be used with GV3G66 + GVAM11 insulating barrier to meet UL 508 Type E rating (7) Use fast acting fuse or time delay Class J (8) Fuse type Class CC Altivar 61 Short Circuit Current Ratings (2) with Circuit Breaker (3) with GV p P (3) with Fuses (3) with Fuses and Type 1 kit (4) Input Voltage 50/60 Hz Y (HP) (kW) (A) Part number Input Rating: (kA) (1) Minimum Inductance (mH) Line Reactor Reference PowerPact (5) Z1, Z2 SCCR (kA) X Minimum Enclosure Volume (in 3 ) GV p P Type E (6) Z1, Z2 GV p P Voltage Rating (V) GV p P Maximum Power (HP) SCCR (kA) X Minimum enclosure Volume (in 3 ) Fuse Ampere Rating (A) Z1, Z2 SCCR (kA) X Minimum enclosure Volume (in 3 ) Fuse Ampere Rating (A) Z1, Z2 SCCR (kA) X Minimum enclosure Volume (in 3 ) Single-phase Input, without line reactor 200/240V single-phase 0.5 0.37 3 ATV61H075M3 5 - - HJL36015 5 4017 - - - 5 1600 15 (7) 5 1078 15 (7) 5 1078 1 0.75 4.8 ATV61HU15M3 5 - - HJL36025 5 4017 GV2P14 240 1 5 1600 25 (7) 5 1078 25 (7) 5 1078 2 1.5 8 ATV61HU22M3 5 - - HJL36040 5 4017 GV3P18 240 3 5 4017 40 (7) 5 1550 25 (7) 5 1550 3 2.2 11 ATV61HU30M3 5 - - HJL36040 5 4017 GV3P18 240 3 5 1920 40 (7) 5 1550 40 (7) 5 1550 5 4 17.5 ATV61HU75M3 5 - - HJL36110 5 6528 GV3P50 240 7.5 5 4032 110 (7) 5 2719 70 (7) 5 2719 7.5 6 27.5 ATV61HD15M3X 5 - - JJL36175 5 6528 GV3P65 240 10 5 5760 175 (7) 5 4036 110 (7) 5 4036 10 8 33 ATV61HD18M3X 5 - - JJL36200 5 13215 - - - - - 200 (7) 5 4900 125 (7) 5 4900 15 11 54 ATV61HD30M3X 5 - - JJL36250 5 13215 - - - - - 250 (7) 5 9640 200 (7) 5 9640 20 15 66 ATV61HD37M3X 5 - - JJL36250 5 13215 - - - - - 250 (7) 5 9640 225 (7) 5 9640 25 18 75 ATV61HD45M3X 10 - - - - - - - - - 300 (7) 10 9640 300 (7) 10 9640 Single-phase input, with line reactor 200/240V Single- phase - 3 13.7 ATV61HU40M3 5 1 RL02502 HJL36060 5 6528 GV3P25 240 3 5 1920 60 (7) 5 1550 45 (7) 5 1550 5 4 17.5 ATV61HU55M3 5 0.8 RL03502 HJL36080 5 6528 GV3P40 240 5 5 2880 70 (7) 5 1987 60 (7) 5 1987 7.5 6 27.5 ATV61HU75M3 22 0.5 RL05502 HJL36110 22 6528 GV3P50 240 7.5 22 4032 110 (7) 22 2719 70 (7) 22 2719 10 8 33 ATV61HD15M3X 22 0.4 RL08002 JJL36175 22 6528 GV3P65 240 10 22 5760 175 (7) 22 4036 110 (7) 22 4036 15 11 54 ATV61HD22M3X 22 0.3 RL10002 JJL36200 22 13215 - - - - - 200 (7) 22 4900 150 (7) 22 4900 20 15 66 ATV61HD30M3X 22 0.2 RL13002 JJL36250 22 13215 - - - - - 250 (7) 22 9640 200 (7) 22 9640 25 18 75 ATV61HD37M3X 22 0.15 RL16002 JJL36250 22 13215 - - - - - 250 (7) 22 9640 225 (7) 22 9640 30 22 88 ATV61HD45M3X 22 0.185 RL20003B14 LAL36400 22 8640 - - - - - 300 (7) 22 9640 300 (7) 22 9640 Short Circuit Current Ratings and branch circuit protection The combinations in the tables have been tested per UL508C (Reference UL file E116875). These ratings are in addition to ratings on the nameplate of the product. The values for the overcurrent protection devices are the maximum allowable amp size. Smaller amp ratings may be used. Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes. The devices are provided with software integral overload and over speed protection for the motor. Protection at 110% of the full load motor current. The motor thermal protection current (ItH) must be set to the rated current indicated on the motor nameplate. (For detail see the programming manual). 75C (167 F) copper conductor with the AWG wire size for all products, except ATV61HC16N4p to ATV61HC63N4p, ATV61HC11Y to ATV61HC80Y: 60C (140F) / 75C (167 F) copper conductor with the AWG wire size. Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kiloAmperes,___Y___Volts maximum, when protected by___Z1___with a maximum rating of___Z2___.

Previous Page
Next Page