Altivar Process 900 Variable Speed Drives Page 54 Altivar Process ATV900 Drive Systems and Altivar Outdoor

54 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 References Variable speed drives Altivar Process ATV900 ATV960 high performance drive systems Input and Output Current Ratings and Dissipated Heat VAC HP kW Max. Input Current Output Current Drive Only Output Current with Bypass or 50 C Rated Typical Dissipated Power at Rated Load (A) (W) 230 1 0.7 3 4.6 4.2 63 2 1.5 5.3 8 6.8 100 3 2.2 7.6 11.2 9.6 138 5 3 13 18.7 15.2 226 7.5 5.5 17.1 25.4 22 289 10 7.5 23.1 32.7 28 401 15 11 34.3 46.8 42 651 20 15 45.5 63.4 54 768 25 18 54.5 78.4 68 860 30 22 67.1 92.6 80 972 40 30 88.6 123 104 1231 50 37 108.5 149 130 1553 60 45 130.4 (1) 175 154 1789 460 1 0.7 1.5 2.2 2.1 60 2 1.5 2.9 4 3.4 84 3 2.2 4 5.6 4.8 115 5 3 7.2 9.3 7.6 173 7.5 5.5 9.2 12.7 10 231 10 7.5 12.5 16.5 14 272 15 11 18.1 23.5 21 378 20 15 24.4 31.7 27 515 25 18 29.9 39.2 34 680 30 22 35.8 46.3 40 739 40 30 48.3 61.5 52 898 50 37 59 74.5 65 1072 60 45 71.8 88 77 1324 75 55 86.9 106 96 1418 100 75 118.1 145 124 1823 125 90 156 173 156 2120 150 110 184 211 180 (2) 2530 200 130 218 250 240 (2) 3150 250 160 280 302 302 (2) 4030 300 200 328 370 (3), (2) 4380 400 250 427 477 (3), (2) 5750 500 310 535 590 (3), (2) 7810 600 400 634 730 (3), (2) 9900 700 500 776 900 (3), (2) 13330 900 630 968 (1) 1140 (3), (2) 16250 (1) Rating only for Normal Duty. (2) See Maximum Ambient Temperature on page 56 for more information on 50 C derating. (2) Consult Schneider Electric.