Modicon M580 Plc Page 3-17 Communication

3/17 Modicon M580 automation platform Ethernet Modbus/TCP network Performance Application response time (continued) I/O Scanning service response time (continued) Below are the TMod In and TMod Out response times: Type of distributed I/O Response time Min. Typical Max. Momentum 170ENT11002 TMod In 1 ms 1 ms 1 ms TMod Out 5 ms 5 ms 5 ms Momentum 170ENT11001 TMod In 4 ms 6 ms 8 ms TMod Out 4 ms 6 ms 8 ms Advantys STB STBNIP2212 TMod In 2 ms 3 ms 4 ms TMod Out 2 ms 3 ms 4 ms The TIOS In/TIOS Out times measured between 2 scan cycles (Ethernet network with switches) are shown below: The number N of CPU scan cycles is shown below: Number of CPU cycles N Min. Typical Max. Modicon M340 platform with BMXNOC0401 and BMXNOE0100WS modules 2 2.5 3 Modicon M580 platform with BMENOC03 p 1 modules Premium platform with TSXETC103 and TSXETY5103 modules Quantum platform with 140NOC771 and 140NOC78 ppp modules Quantum platform with 140NOC77101 and 140NOC78 p 00 modules Modicon M580 platform with BMEP58 pppp modules Modicon M340 BMXP342020/2030 CPUs Premium TSXP5726/3634M , TSXP5726/2823M and TSXP5736/4823AM CPUs Premium TSXP5746/56/6634M CPUs 1 2 Quantum 140CPU65150/60 CPUs Performance (continued) 0 5 10 15 20 25 1 5 10 20 30 40 50 60 Number of devices scanned Time (ms) Processors: page 1/20 I/O architectures: page 2/2 Ruggedized Modicon M580 modules: page 4/2 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10