Modicon Quantum Automation Platform Page 3-16 Discrete and analog I/O modules

2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 3/16 Selection guide Modicon Quantum automation platform 0 Analog I/O modules Current/voltage, temperature probe, thermocouple inputs Type Analog input modules, 8 channels and 16 channels Number of channels 8 differential 16 differential or 16 with common point 8 differential Input range 420 mA 15 V 025 mA 020 mA 420 mA 020 mA, 20 mA, 420 mA 010 V, 10 V 05 V, 5 V 15 V Resolution 12 bits 0...25 mA: 025,000 points 0...20 mA: 020,000 points 4...20 mA: 016,000 points (default) 4...20 mA: 0...4095 points 14/15/16 bits depending on range I/O addresses 9 input words 17 input words 9 input words Isolation between channels (max.) 30 V c 200 V c 135 V a rms Bus current required 240 mA 360 mA 280 mA Maximum dissipated power 2 W 5 W 2.2 W External power supply (U s ) Not required External fuse Online modification of configuration (1) Yes Functional safety certification Non-interfering Approvals UL 508, CSA 22.2-142, e , FM Class 1 Div. 2, ATEX Zone 2/22 (2) Type of module 140ACI03000 140ACI04000 140AVI03000 Page 3/22 (1) For online modification of configuration, see page 2/37. (2) Only Conformal Coating versions, depending on model, are ATEX Zone 2/22 certified. For more information, see pages 8/2 to 8/9. 3/16

Previous Page
Next Page