Analog I/O modules

Current/voltage outputs, mixed I/O

Type Analog output module, 4 channels and 8 channels Number of channels 4 8 4 Input range 420 mA 025 mA 020 mA 420 mA 010 V 05 V 10 V 5 V Resolution 12 bits 025 mA: 025,000 points 020 mA: 020,000 points 420 mA: 016,000 points (default) 420 mA: 04095 points 12 bits I/O addresses 4 output words 8 output words 4 output words Isolation between channels 500 V a at 4763 Hz or 750 V c for 1 minute None 500 V a at 4763 Hz for 1 minute Bus current required 480 mA 550 mA 700 mA Maximum dissipated power 5.3 W 5.0 W 4.5 W External power supply (U

s

) 12...30 V c 6...30 V c max. External fuse 0.063 mA, 250 V 3AG fast-blow (2) Online modification of configuration (1) Yes Functional safety certification Non-interfering Approvals UL 508, CSA 22.2-142, e , FM Class 1 Div. 2, ATEX Zone 2/22 (3) Type of module

140ACO02000 140ACO13000 140AVO02000

Page 3/22 (1) For online modification of configuration, see page 2/37. (2) External fuse to be used on the Master Override signal when it is connected to an external source.