Modicon Quantum Automation Platform Page 7-29 I/O prewired systems and process power supplies

7/29 Selection, references Selection of protection on the power supply primaries Type of mains supply a 115 V single-phase a 230 V single-phase Power supply Thermal-magnetic circuit-breaker (1) Gg fuse Thermal-magnetic circuit-breaker (2-pole) Gg fuse ASIABLB3002 GB2 p B07 MG24517 (2) 2 A GB2DB06 MG24516 (2) 2 A ASIABLB3004 GB2 p B08 MG24518 (2) 4 A GB2DB07 MG17453 (2) 2 A ASIABLD3002 GB2 p B07 MG24517 (2) 2 A GB2DB06 MG24516 (2) 2 A ASIABLD3004 GB2 p B08 MG24518 (2) 4 A GB2DB07 MG17453 (2) 2 A ASIABLM3024 GB2 p B07 MG24517 (2) 2 A GB2DB06 MG17453 (2) 2 A (1) Single-phase protection, replace p by C ; 2-pole protection, replace p by D. (2) UL certified circuit breaker. References Input voltage Secondary Auto-protect reset Earth fault detection Reference Weight kg/ lb Output voltage Nominal power Nominal current Single phase (N-L1) or 2-phase (L1-L2) a 100240 V - 15 %, + 10 % 50/60 Hz c 30 V 72 W 2,4 A Auto No ASIABLB3002 0.800 / 1.764 144 W 4,8 A Auto No ASIABLB3004 1.300 / 2.866 72 W 2,4 A Auto Yes ASIABLD3002 0.800 / 1.764 144 W 4,8 A Auto Yes ASIABLD3004 1.300 / 2.866 c 30 V 72 W 2,4 A Auto No ASIABLM3024 1.300 / 2.866 c 24 V 72 W 3 A Power supplies and transformers Phaseo Regulated switch mode power supplies ASIABL Power supplies for AS-Interface cabling system ASIABL p 3002 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10