Powerpact B Frame Circuit Breakers Page 36 Accesories and Auxiliaries

PowerPact B-Frame 15 to 125 A Circuit Breakers Accessories and Auxiliaries Auxiliary and Alarm Indication Contacts Auxiliary Switch (OF) / Alarm Switch (SD). Indication contacts provide remote information of the circuit breaker status and can thus be used for indications, electrical interlocking, relays, etc. They are 1A1B common point changeover type contacts, with a normally open (NO) contact and a normally closed (NC) contact. Open/Closed - Auxiliary Switch (OF) Indicates the position of the circuit breaker contacts. Trip Indication - Trip Alarm Switch (SD) Indicates that the circuit breaker has tripped due to: an electrical fault (overload, short circuit) the operation of a shunt trip or an undervoltage trip the push-to-trip button. The activation of the push-to-trip button resets when the circuit breaker is reset. Electrical Characteristics of Indication Contacts Characteristics Rated thermal current (A) 5 Minimum load 5 mA at 17 Vdc Utilization Cat. (IEC 60947-5-1) AC12 AC15 DC12 DC13 DC14 Operational current (A) 24 Vac/Vdc 5 2.5 1 48 Vac/Vdc 5 2.5 1.2 0.2 110-127 Vac / 110 Vdc 5 4 0.6 0.35 0.05 220/240 Vac 5 3 - 250 Vdc - 0.3 0.05 0.03 380/440 Vac 5 2.5 - 660/690 Vac 5 0.11 - UL489, CSA C22.2 No. 5 Ampere Rating (A) Pilot Duty Standard (A) 11 48 Vac 5 - 120 Vac 5 3 240 Vac 5 1.5 480 Vac 5 0.75 600 Vac - 0.6 48 Vdc 2.5 - 110 Vdc 0.8 - 250 Vdc 0.3 - 36 0611CT1603 11. Certified to UL 489 and UL 508 per NEMA Type B600 of Rating Codes for AC Control-circuit Contacts at 50 and 60 Hz table.