Powerpact B Frame Circuit Breakers Page 87 Catalog Numbers

Catalog Numbers PowerPact B-Frame 15 to 125 A Circuit Breakers Catalog Numbers PowerPact B-Frame Circuit Breaker Catalog Numbers UL 489 Circuit Breaker Ratings Circuit breaker type BD BG BJ BK Number of poles 1 2-4 1 2-4 1 2-4 1 2 Amperage range (A) 15-125 15-125 15-125 15-125 15-125 15-125 15-30 15-30 UL/CSA/NOM (kA rms) 208Y/120 Vac 25 65 100 240 Vac 25 65 100 480Y/277 Vac 18 35 65 480 Vac - 18 - 35 - 65 - 65 600Y/347 Vac 14 18 25 65 PowerPact B-Frame 1P Unit-Mount Single Phase Circuit Breakers OFF B-Frame, 1P, Single Phase Rated, with EverLink Connectors, Factory-Sealed Trip Unit (Suitable for Reverse Connection) Current Rating at 40C (A) Fixed AC Magnetic Trip (A) Interrupting Rating-Standard (80%) Rated Hold Trip D G J 15 400 600 BDL16015 BGL16015 BJL16015 20 400 600 BDL16020 BGL16020 BJL16020 25 400 600 BDL16025 BGL16025 BJL16025 30 400 600 BDL16030 BGL16030 BJL16030 35 400 600 BDL16035 BGL16035 BJL16035 40 400 600 BDL16040 BGL16040 BJL16040 45 400 600 BDL16045 BGL16045 BJL16045 50 480 720 BDL16050 BGL16050 BJL16050 60 640 960 BDL16060 BGL16060 BJL16060 70 640 960 BDL16070 BGL16070 BJL16070 80 800 1200 BDL16080 BGL16080 BJL16080 90 1000 1500 BDL16090 BGL16090 BJL16090 100 1000 1500 BDL16100 BGL16100 BJL16100 110 1000 1500 BDL16110 BGL16110 BJL16110 125 1000 1500 BDL16125 BGL16125 BJL16125 0611CT1603 87